For use with Rotary Converter
for 3 phase electronic equipment such as CNC/PLC machines, AC/DC
drives, and all voltage-sensitive equipment. Provides +/- 5% voltage
stabilization.
The
normal operating voltage of the Rotary Phase Converter is
208-230VAC. The output voltage of the Rotary Phase Converter is
normally higher than the input voltage under no load and light
load conditions. In applications with high single phase voltage
(greater than 230V), the no load or light load output voltage
may be excessive. Some CNC equipment will not work properly at
the higher output voltage.
The
Phase-A-Matic™ Voltage Stabilizer is designed to reduce this
higher voltage to nearer the input voltage. It will also keep
the output voltage stable during peak loads, thus helping CNC
equipment and other voltage sensitive equipment to operate
properly.
Running
very small motors alone on a Rotary Converter that is 3 times or
more larger may not reduce the output voltage sufficiently, in
which case the smaller motor may run hot. For these cases, to
reduce cost it may be possible to use a dedicated Voltage
Stabilizer sized to the requirements of the problem motor only.
Consult factory.
Supplied in a
NEMA type 1 enclosure with various sizes of knockouts.
Intended
for indoor use only in dry locations, but can be placed in a
rain tight enclosure for use in wet or damp locations.
Select
a Voltage Stabilizer at least as large as the load it will
operate. It does not have to be as large as the Rotary Phase
Converter being used.
|